Experimental determination of incident energy (IE) in arc flash testing requires integrating calorimetry, signal acquisition, and thermal processing; when performed separately, these tasks may increase operator intervention and hinder data-flow standardization. This study developed and experimentally evaluated an integrated system for IE measurement in arc flash tests. The architecture combines copper calorimeters instrumented with Type K thermocouples and arranged according to the spatial configuration adopted in the IEEE Std 1584-2018 test program, galvanically isolated data acquisition, and a LabVIEW-based virtual instrument (VI) for monitoring, thermal-parameter identification, Shomate-based enthalpy calculations, and data storage. The calorimeters satisfied the functional-verification criterion of IEC 61482-1-1, and the VI-based IE calculation showed numerical agreement with an independently implemented reference calculation. Across 18 tests, comprising 10 tests with vertical electrodes in open air (VOA) and 8 with horizontal electrodes in open air (HOA), measured IE remained below the corresponding IEEE Std 1584-2018 estimates, with relative differences from -29.3 % to -2.6 % and a mean of -12.7 %. This ordering was consistent under the evaluated conditions, although the magnitude of the difference varied among tests and should not be generalized beyond the investigated experimental set. The proposed integration consolidates calorimetric IE acquisition, processing, and comparison into a single workflow.