Answers are grounded in this paper and cite their sources.
Reducing building CO2 emissions requires energy-efficient heating, ventilation, and air conditioning (HVAC) systems that can operate with renewable electricity. The building-scale performance of thermoelectric radiant ceiling panels with dedicated outdoor air supply (TERP + DOAS) under different power-supply options remains less explored. This study investigates the effects of HVAC system configuration on annual energy use and the effects of PV, battery, and grid supply on grid dependence and CO2 emissions. An office in Jaipur, India, with dimensions of 11.5 m×6.1 m×2.8 m, is evaluated using six HVAC system configurations and five power-supply scenarios. An analytical framework links annual HVAC energy demand with hourly energy allocation, photovoltaic (PV) generation, battery storage, grid supply, CO2 emissions, PV curtailment, and unmet demand. The novelty lies in combining building-scale assessment of multiple HVAC system configurations with case-specific PV and battery sizing and hourly energy dispatch under different power-supply scenarios. TERP+DOAS uses 4440 kWh/yr of HVAC electricity, 24.2%, 35.7%, and 54.5% lower than DOAS, TERP with cooling tower, and TERP with chiller, respectively. Under PV + battery + grid, grid supply is 1059 kWh/yr, with CO2 emissions of 769.9 kg/yr and a reduction of 2458.0 kg/yr compared with grid-only supply.
No takes yet. Share an insight, caveat, or question.
Mishra et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: