Answers are grounded in this paper and cite their sources.
Identifies abnormal failure modes impacting HVDC applications, suggesting recommendations for enhanced reliability.
Detecting and disconnecting faults is of utmost importance in power systems to prevent damage, outages and limit the impact on the surrounding grid. However, there are faults that may not be detected by protective functions and therefore do not interrupt the operation. Such faults, which have not been considered during the design of an HVDC system despite causing negative operational impacts, are referred to as abnormal failure modes in this paper. Data from three cases of abnormal failure modes in point-to-point HVDC systems are presented. The first case regards a prolonged subsequential failure of a DC filter capacitor for an LCC-HVDC link. The second case presents a measurement disturbance resulting in power oscillations from a VSC-HVDC link. The third case shares details of an overload scenario of a grounding impedance due to DC voltage unbalance from asymmetric corona discharges. This study shares details from these failures and suggests recommendations based on the presented abnormal failure modes in HVDC applications, including multi-terminal HVDC systems.
No takes yet. Share an insight, caveat, or question.
Pettersson et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: