Answers are grounded in this paper and cite their sources.
This study investigates the fire extinguishing effectiveness and mechanisms of dry water modified by ammonium dihydrogen phosphate, sodium chloride, magnesium hydroxide, and potassium acetate in confined spaces. Through the analysis of temperature, oxygen concentration, and thermogravimetric data, the fire suppression efficiency of modified dry water was explored. The critical oxygen concentration and mass loss rate were calculated using a diffusion combustion model to reveal the underlying extinguishing mechanisms. The experimental results show that the fire extinguishing efficiency of modified dry water was significantly higher than that of pure dry water. Notably, the fire extinguishing effect of side spraying was markedly superior to that of top spraying, achieving a temperature reduction of 60% and a minimum oxygen concentration of 10.68%. Under top-spray mode, MHDW reduced the extinguishing time by 48.7%compared to DW, while under side-spray mode, SCDW reduced the extinguishing time and agent consumption by 44.2% and 34.3%, respectively. ADPDW and PADW increased the apparent activation energy, whereas SCDW and MHDW reduced it. Based on theoretical calculations, it can be concluded that effective cooling is the dominant physical suppression mechanism for dry water in liquid fuel fires. The findings suggest that dry water fire extinguishing agents have good application prospects in confined spaces such as tunnels and cabins, and may become a good alternative or auxiliary.